MGM Type Light Mechanical Excitation Element
MGM Type Heavy Mechanical Excitation Element
MGM Type High Temperature Excitation Element
MGM Type Replacement Element Without Excitation Element

Busbar Transfer Current Switching Contacts
External or Internal Environment
Busbar Transfer Voltage: Up to 350V level
Busbar Transfer Current: Up to 1600A level
Related Standards
IEC 62271-102 / ANNEX-B
TS EN 62271-102 / ANNEX-B

Internal Normal Load Breaker
Indoor
Class E3 General Purpose Switch
M1 Mechanical Strength
Rated Current: Up to 630A
Active Based Rated Load Breaking Current: 630A – 100 Opening Closing Operation
Short-Time Withstand Current / Duration: 20kA / 1s
Peak Withstand Current: 52kA peak
Short-Circuit Closing Current (Peak): 42kA
Rated Voltage: 12kV-36kV

Internal Fused Earthed Load Disconnector
Indoor
E3 Class General Purpose Switch
M1 Mechanical Strength
Rated Current: According to fuse changeover element
Active Based Rated Load Breaking Current: 630A – 100 Opening Closing Operation
Short Time Withstand Current / Duration: 20kA / 1s
Peak Withstand Current: 52kA peak
Short Circuit Closing Current (Peak): 42kA
Rated Voltage: 12kV-36kV

Internal Earthing Load Break Switch
Indoor
Class E3 General Purpose Switch
M1 Mechanical Strength
Rated Current: Up to 630A
Active Based Rated Load Breaking Current: 630A – 100 Opening Closing Operation
Short-Time Withstand Current / Duration: 20kA / 1s
Peak Withstand Current: 52kA peak
Short Circuit Closing Current (Peak): 42kA
Rated Voltage: 12kV-36kV

VBD: Vertical Break Disconnector
VBDE: Single Earthing Switch Vertical Break Disconnector
VBDEE: Double Earthing Switch Vertical Break Disconnector
Single phase and three phase models are available.

DA:Internal Normal Disconnector
DT:Internal Grounding Disconnector
DS:Internal Fused Disconnector
DST:Internal Fused Grounding Disconnector
HA:External Normal Disconnector
HT:External Grounding Disconnector
HS:External Fused Disconnector
HST:External Fused Grounding Disconnector
Single phase and three phase models are available.

HD99: External Environment, High Voltage
Disconnector, Hand Control Mechanism
MVHD: External Environment, Medium Voltage Disconnector,
Hand Control Mechanism
Internal Arm: Internal Environment, Medium Voltage Disconnector,
Hand Control Mechanism

Induced Current Switching Contacts
External or Internal Environment
Special for Earthing Switches
Class A or Class B
Related Standards
IEC 62271-102 / EK-C
TS EN 62271-102 / EK-C

Single phase and three phase models are available.

Can be designed as internal and external.

XS-1036:Voltage Detector

Air Breaking Switchgear Limited Purpose External Load Breaker
External Environment
E1 Class Limited Purpose Switch
M2 (10,000 CO) Mechanical Strength
Rated Current: Up to 2000A
Active Based Rated Load Breaking Current: 400A
Short Time Withstand Current / Duration: 31.5kA / 1s-3s
Peak Withstand Current: 82kA peak
Short Circuit Closing Current (Peak): –
Rated Voltage: 12kV-36kV

General Purpose External Load Break Switch with Air Breaking Switchgear
External Environment
E1 Class General Purpose Switch
M2 (10,000 CO) Mechanical Strength
Rated Current: Up to 2000A
Active Based Rated Load Breaking Current: 400A
Short Time Withstand Current / Duration: 31.5kA / 1s-3s
Peak Withstand Current: 82kA peak
Short Circuit Closing Current (Peak): Up to 50kA
Rated Voltage: 12kV-36kV

Air Breaking Switchgear Limited Purpose External Load Breaker
External Environment
E1 Class Limited Purpose Switch
M2 (10,000 CO) Mechanical Strength
Rated Current: Up to 2000A
Active Based Rated Load Breaking Current: 400A
Short Time Withstand Current / Duration: 31.5kA / 1s-3s
Peak Withstand Current: 82kA peak
Short Circuit Closing Current (Peak): –
Rated Voltage: 12kV-36kV

Single phase and three phase models are available.

Can be designed as internal or external.