You are here:

Showing 433–441 of 441 results

Ürünler

Structure
Three-core, multi-wire, copper conductor, very low dielectric losses
PROTOTHEN®-X (XLPE) insulation, special inner and outer semi-conductor layers that homogenize the electrical field, suitable cross-section against high short-circuit currents
and specially added copper screen, flat galvanized steel wire armor and galvanized steel holding tape, halogen-free, does not create a dense smoke layer during fire and LSOH outer sheathed medium voltage energy cables

Technical Information
These cables are manufactured in accordance with TS IEC 60502-2.
– Permissible operating temperature: 90 ºC
– Permissible short circuit temperature: 250 ºC
(For short circuit time t ≤ 5 sec.)
They are tested in accordance with the following standards:
LS (Low Smoke) Test: IEC 61034-1/2
Burning Droplet Test: IEC 60332-1-3
HF (Halogen Free) Test: IEC 60754-1/2
FR (Flame Resistance) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C

Places of Use
These cables, which have very low electrical losses compared to their counterparts, are used in electrical energy supply of residential and industrial areas where short circuit currents are high and in networks where load increases are expected, outdoors, in cable ducts and indoors.

For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.

Structure
Multi-core, solid or stranded, copper conductor PROTOTHEN®-X(XLPE) insulated, concentric copper neutral conductor, PROTODUR® (PVC) outer sheathed power cables.

Technical Information
-Manufactured according to TS IEC 60502-1.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– CPR (Construction Materials Directive) Test: EN 60332-1-2
– Test Voltage (AC): 3.5 kV

Areas of Use
They are generally used underground for city networks, street lighting, home connections and similar purposes. In case of damage to the cables due to digging, the concentric neutral conductor ensures that the switch or fuse at the cable head opens the circuit immediately.

For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.

Structure
Multi-core, solid or stranded, copper conductor PROTOTHEN®-X(XLPE) insulated, concentric copper neutral conductor, PROTODUR® (PVC) outer sheathed power cables.

Technical Information
-Manufactured according to TS IEC 60502-1.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– CPR (Construction Materials Directive) Test: EN 60332-1-2
– Test Voltage (AC): 3.5 kV

Areas of Use
They are generally used underground for city networks, street lighting, home connections and similar purposes. In case of damage to the cables due to digging, the concentric neutral conductor ensures that the switch or fuse at the cable head opens the circuit immediately.

For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.

Structure
Single or multi-core, single or multi-wire, copper conductor, PROTOTHEN®-X (XLPE) insulated, PROTODUR® (PVC) outer sheathed energy cables.

Technical Information
-Manufactured according to TS IEC 60502-1.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– CPR (Construction Materials Directive) Test: EN 60332-1-2
– Test Voltage (AC): 3.5 kV

Areas of Use
They are used as energy, network and lighting cables outdoors, in cable ducts, underground, and in fresh and salt water when specially produced.

For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.

Structure
Single or multi-core, single or multi-wire, copper conductor, PROTOTHEN®-X (XLPE) insulated, PROTODUR® (PVC) outer sheathed energy cables.

Technical Information
-Manufactured according to TS IEC 60502-1.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– CPR (Construction Materials Directive) Test: EN 60332-1-2
– Test Voltage (AC): 3.5 kV

Areas of Use
They are used as energy, network and lighting cables outdoors, in cable ducts, underground, and in fresh and salt water when specially produced.

For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.

Structure
Single or multi-core, single or multi-wire, copper conductor, PROTOTHEN®-X (XLPE) insulated, PROTODUR® (PVC) outer sheathed energy cables.

Technical Information
-Manufactured according to TS IEC 60502-1.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– CPR (Construction Materials Directive) Test: EN 60332-1-2
– Test Voltage (AC): 3.5 kV

Areas of Use
They are used as energy, network and lighting cables outdoors, in cable ducts, underground, and in fresh and salt water when specially produced.

For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.

Structure
Single or multi-core, single or multi-wire, copper conductor PROTOTHEN®-X (XLPE) insulated, galvanized round steel wire armored, PROTODUR® (PVC) outer sheathed energy cables. (Aluminum in single-core cables.)

Technical Information
-They are manufactured according to TS IEC 60502-1.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– CPR (Construction Materials Directive) Test: EN 60332-1-2
– Test Voltage (AC): 3.5 kV
– Galvanized Round Steel Wire Armored

Areas of Use
These cables are very resistant to mechanical external effects thanks to the armor made of galvanized round steel wires on them. They are suitable for heavy operating, laying and assembly conditions. They are used underground and in fresh and salt water when specially produced.

For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.

Structure
Single or multi-core, single or multi-wire, copper conductor PROTOTHEN®-X (XLPE) insulated, galvanized round steel wire armored, PROTODUR® (PVC) outer sheathed energy cables. (Aluminum in single-core cables.)

Technical Information
-They are manufactured according to TS IEC 60502-1.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– CPR (Construction Materials Directive) Test: EN 60332-1-2
– Test Voltage (AC): 3.5 kV
– Galvanized Round Steel Wire Armored

Areas of Use
These cables are very resistant to mechanical external effects thanks to the armor made of galvanized round steel wires on them. They are suitable for heavy operating, laying and assembly conditions. They are used underground and in fresh and salt water when specially produced.

For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.

Structure
Multi-core, multi-wire, copper conductor, PROTOTHEN®-X (XLPE) insulated, galvanized flat steel wire armor, cross-holding steel tape, PROTODUR® (PVC) outer sheathed energy cables.

Technical Information
-Manufactured according to TS IEC 60502-1.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– CPR (Construction Materials Directive) Test: EN 60332-1-2
– Test Voltage (AC): 3.5 kV
– Galvanized Flat Steel Wire Armored

Areas of Use
These cables are very resistant to mechanical external effects thanks to the armor made of flat steel wires on them. They are suitable for heavy operating, laying and assembly conditions. They are used underground and in fresh and salt water when specially produced.

For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.