Dahili Sigortalı Topraklı Yük Ayırıcıları (SFCE)
Internal Fused Earthed Load Disconnector
Indoor
E3 Class General Purpose Switch
M1 Mechanical Strength
Rated Current: According to fuse changeover element
Active Based Rated Load Breaking Current: 630A – 100 Opening Closing Operation
Short Time Withstand Current / Duration: 20kA / 1s
Peak Withstand Current: 52kA peak
Short Circuit Closing Current (Peak): 42kA
Rated Voltage: 12kV-36kV
Aynı Markalı Diğer Ürünlerimiz
Insulating Carpets
External and/or Internal Environment
Rated Voltage: 15kV and 36kV
Fuse Replacement Clip
External and/or Internal Environment
Rated Voltage: 7.2kV-36kV
DSA: Internal Fuse Bases
HSA: External Fuse Bases
Rated Current: Current Limiting Backup Fuse
Depending on Replacement Element.
MGM Type Light Mechanical Excitation Element
MGM Type Heavy Mechanical Excitation Element
MGM Type High Temperature Excitation Element
MGM Type Replacement Element Without Excitation Element
Internal Earthing Load Break Switch
Indoor
Class E3 General Purpose Switch
M1 Mechanical Strength
Rated Current: Up to 630A
Active Based Rated Load Breaking Current: 630A – 100 Opening Closing Operation
Short-Time Withstand Current / Duration: 20kA / 1s
Peak Withstand Current: 52kA peak
Short Circuit Closing Current (Peak): 42kA
Rated Voltage: 12kV-36kV
Internal Normal Load Breaker
Indoor
Class E3 General Purpose Switch
M1 Mechanical Strength
Rated Current: Up to 630A
Active Based Rated Load Breaking Current: 630A – 100 Opening Closing Operation
Short-Time Withstand Current / Duration: 20kA / 1s
Peak Withstand Current: 52kA peak
Short-Circuit Closing Current (Peak): 42kA
Rated Voltage: 12kV-36kV
Air Breaking Switchgear Limited Purpose External Load Breaker
External Environment
E1 Class Limited Purpose Switch
M2 (10,000 CO) Mechanical Strength
Rated Current: Up to 2000A
Active Based Rated Load Breaking Current: 400A
Short Time Withstand Current / Duration: 31.5kA / 1s-3s
Peak Withstand Current: 82kA peak
Short Circuit Closing Current (Peak): –
Rated Voltage: 12kV-36kV
Busbar Transfer Current Switching Contacts
External or Internal Environment
Busbar Transfer Voltage: Up to 350V level
Busbar Transfer Current: Up to 1600A level
Related Standards
IEC 62271-102 / ANNEX-B
TS EN 62271-102 / ANNEX-B