- Ana Sayfa
- Prysmian
- Telecom Solutions (Low Current Cables)
- Fiber Optic Cable Accessories
- Wall Mounted Termination Boxes
- WM060-02 MDWB – Medium Distribution Wall Box
WM060-02 MDWB – Medium Distribution Wall Box
Features and Benefits
• For internal and external use.
• Can be supplied with single element or single circuit trays. Single
element splice capacity is 168 fibres. Single Circuit splice capacity is 112
fibres. Single circuit splice trays are a single tray with two separate
storage areas.
• Note: For use with 1.5mm splice protectors. Crimp splices can also be
used in the single element trays but the capacity is reduced to 6 fibres per
tray.
• Each box comes supplied with a top and bottom routing manifold for fibre
routing to the splice trays.
• All fibres are positively managed to maintain a 30mm minimum bend
radius within the wall box.
• Splice trays hinge upwards individually, allowing full access to spliced
fibres without disturbance to live fibres in adjacent trays.
• The box is suitable for Riser applications.
• Cables can enter / exit from the top or bottom face of the box.
• The box is sealed to IP55 and the boxes are moulded from UV stable
material to prevent discolouring.
• The boxes are made using flame retardant UL94-V0 rated materials
Technical Data
• Number of Input cable ports: 1 (can also be used for in-line pass through). Note output ports can also
be used as additional input ports.
• Number of Output cable ports: 32 for 3-6mm cables (16 on top and 16 on bottom face of box)
4 for 6-12mm cables (2 on top and 2 on bottom face of box).
• Maximum Input cable diameter (mm): 12 (M20 Cable gland)
• Maximum Output cable diameter (mm): 3-6 (32 ports), 6-12 (4 ports)
• Maximum number of splice trays: 14 Single Element Trays = 168 fibres
28 Single Circuit = 112 fibres on 4f per trays basis (note = 14 double SC
trays where each tray has two storage areas)
• Required space envelope (mm): (w) 250 x (h) 280 x (d) 100.
• Operating temperature: -20oC to + 50oC (5 to 95% RH)
• Material:-
• Box (Dark Grey): FR ABS Dark Grey (RAL7030)
• Box (White): FR ABS White (RAL9016)
• Splice trays: FR ABS White (RAL9016)
• Testing:-
• Closure sealing: IP55 – External product only
• Optical: Tested 1310nm,1550nm and 1625nm
• Dry heat: BS EN 60068-2-2 Test Bb
• Damp heat: IEC 60068-2-3: 1969
• Change of temperature: IEC 60068-2-14: 1984
• Vibration: IEC 60068-2-6: 1995
• Shock: IEC 60068-2-27: 1987
Ürün teknik özellik ve detayları için PDF ikonuna tıklayarak detayları görüntüleyebilir, dosyayı indirebilir veya istediğiniz adrese mail yolu ile ulaştırabilirsiniz.
Aynı Markalı Diğer Ürünlerimiz
Structure
The center tube contains the optical fibers and waterproof material, forming the cable core. Glass yarn material is applied around the cable core to increase dielectric strength. Black colored PE sheath is applied on the glass yarn material.
Technical Information
– Temperature in fixed conditions: -25 °C, +70 °C
– Temperature in moving conditions: -10 °C, +50 °C
– Minimum Operating Temperature: -25 ºC
– Maximum Operating Temperature: 70 ºC
– Conductor Structure: Rigid
– Bending Radius: Min 15xD
– Lead-free
Areas of Use
These center tube, unarmored fiber optic cables are designed for use in ducts.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
The center tube contains the optical fibers and waterproof material, forming the cable core. Glass yarn material is applied around the cable core to increase dielectric strength. Black colored PE sheath is applied on the glass yarn material.
Technical Information
– Temperature in fixed conditions: -25 °C, +70 °C
– Temperature in moving conditions: -10 °C, +50 °C
– Minimum Operating Temperature: -25 ºC
– Maximum Operating Temperature: 70 ºC
– Conductor Structure: Rigid
– Bending Radius: Min 15xD
– Lead-free
Areas of Use
These center tube, unarmored fiber optic cables are designed for use in ducts.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
The center tube forms the cable core by containing optical fibers and waterproof material. To increase dielectric strength, glass yarn material is applied around the cable core. To protect the cable core from external factors, corrugated steel tape armor application is made, both sides of which are coated with copolymer material. Black colored PE sheath is applied on top of the armor.
Technical Information
– Temperature in fixed conditions: -25 °C, +70 °C
– Temperature in moving conditions: -10 °C, +50 °C
– Minimum Operating Temperature: -25 ºC
– Maximum Operating Temperature: 70 ºC
– Conductor Structure: Rigid
– Bending Radius: Min 15xD
– Lead-free
Areas of Use
These center tube armored fiber optic cables are designed for duct or direct burial, outdoor environment cables.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
The center tube forms the cable core by containing optical fibers and waterproof material. To increase dielectric strength, glass yarn material is applied around the cable core. To protect the cable core from external factors, corrugated steel tape armor application is made with copolymer material on both sides. Black colored PE sheath is applied on the armor.
Technical Information
– Temperature in fixed conditions: -25 °C, +70 °C
– Temperature in moving conditions: -10 °C, +50 °C
– Minimum Operating Temperature: -25 ºC
– Maximum Operating Temperature: 70 ºC
– Conductor Structure: Rigid
– Bending Radius: Min 15xD
– Lead-free
Areas of Use
These center tube armored fiber optic cables are designed for duct or direct burial, outdoor environment cables.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
The center tube forms the cable core by containing optical fibers and waterproof material. To increase dielectric strength, glass yarn material is applied around the cable core. To protect the cable core from external factors, corrugated steel tape armor application is made, both sides of which are coated with copolymer material. Black colored PE sheath is applied on top of the armor.
Technical Information
– Temperature in fixed conditions: -25 °C, +70 °C
– Temperature in moving conditions: -10 °C, +50 °C
– Minimum Operating Temperature: -25 ºC
– Maximum Operating Temperature: 70 ºC
– Conductor Structure: Rigid
– Bending Radius: Min 15xD
– Lead-free
Areas of Use
These center tube armored fiber optic cables are designed for duct or direct burial, outdoor environment cables.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Multi-core, single or multi-wire copper conductor, special flame-resistant separator layer, special synthetic insulation, concentric copper conductor, special synthetic outer sheath, flame-retardant, halogen-free, non-smoking and 180 minutes flame-resistant energy and control cables according to IEC 60331-21.
Technical Information
– Manufactured in accordance with TS HD 604 S1 5G.
– Permissible operating temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC
– Conductor Structure: Rigid
– LS (Low Smoke) Test: IEC 61034 -1/2
– Burning Droplet Test: IEC 60332-1-3
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C
– FE (Current Conduction) Test: IEC 60331-21
Areas of Use
These cables are used in indoor and outdoor areas such as schools, hospitals, meetings and shopping malls where there are mandatory safety precautions against fire.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Multi-core, single or multi-wire copper conductor, special flame-resistant separator layer, special synthetic insulation, concentric copper conductor, special synthetic outer sheath, flame-retardant, halogen-free, non-smoking and 180 minutes flame-resistant energy and control cables according to IEC 60331-21.
Technical Information
– Manufactured in accordance with TS HD 604 S1 5G.
– Permissible operating temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC
– Conductor Structure: Rigid
– LS (Low Smoke) Test: IEC 61034 -1/2
– Burning Droplet Test: IEC 60332-1-3
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C
– FE (Current Conduction) Test: IEC 60331-21
Areas of Use
These cables are used in indoor and outdoor areas such as schools, hospitals, meetings and shopping malls where there are mandatory safety precautions against fire.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Multi-core, fine multi-wire copper conductor, special synthetic insulation, special filling layer, special synthetic outer sheath, flame retardant, halogen-free energy cables.
Technical Information
– Manufactured in accordance with TSE 13751.
– Permissible operating temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC
– Conductor Structure: Flexible
– LS (Low Smoke) Test: IEC 61034 -1/2
– Burning Droplet Test: IEC 60332-1-3
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C
– CPR (Construction Materials Directive) Test: EN 50399
Areas of Use
They are used in facilities with a fire risk such as hotels, hospitals, shopping malls, power plants and data processing centers, and in facilities where there are many people and valuable devices where mass transportation is carried out by rail systems. These cables do not transmit flame during a fire, do not create a dense smoke layer and do not create an environment suitable for corrosion, thus ensuring the safety of life and property.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Single-core, multi-wire, copper conductor, PROTOTHEN®–X (XLPE) insulation with very low dielectric losses, special inner and outer semiconductor layers that homogenize the electrical field, copper screen with a section suitable for high short-circuit currents and specially reinforced, water-swellable tape layer, aluminum protective sheath and polyethylene outer sheath high voltage energy cables. The screen is watertight in longitudinal and radial directions. If desired, longitudinal watertightness can be provided in the conductor.
Technical Information
– They are manufactured according to TS 10382 IEC 60840.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– Test Voltage (AC): 2.5Uo (30 min.)
Areas of Use
These cables are located underground, in concrete channels and / or PVC-PE pipes, in places where aerial high voltage lines cannot enter city centers due to safety, health and visual pollution, and they connect energy production / distribution places transformer centers to national / international distribution networks.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Medium voltage energy cables with single core, multi-wire, copper conductor, very low dielectric loss PROTOTHEN®-X (XLPE) insulation, special inner and outer semi-conductor layers that homogenize the electrical field, specially added copper screen against high short circuit currents, LSOH outer sheath.
Technical Information
– They are manufactured in accordance with TSE K 204 and based on IEC 60502-2.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– Test Voltage (AC): 3.5Uo
Areas of Use
These cables, which have very low electrical losses compared to their counterparts, are used in electrical energy supply of residential and industrial areas where short circuit currents are high and in networks where load increases are expected, outdoors, in cable ducts, indoors and underground. When specially produced, they are used in fresh and salt water.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Three-core, multi-wire, copper conductor, PROTOTHEN®-X (XLPE) insulation with very low dielectric losses, special inner and outer semi-conductor layers that homogenize the electrical field, specially added copper screen with a suitable cross-section against high short circuit currents, flat galvanized steel wire armor and galvanized steel holding tape, LSOH outer sheathed medium voltage energy cables.
Technical Information
-They are manufactured according to TS IEC 60502-2.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– Test Voltage (AC): 3.5Uo
– Galvanized Flat Steel Wire Armored
Areas of Use
These cables, which have very low electrical losses compared to their counterparts, are used in electrical energy supply of large residential and industrial areas with large short circuit currents and in networks where load increases are expected, outdoors, in cable ducts, indoors and underground. When specially produced, they are used in fresh and salt water.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Medium voltage energy cables with single core, multi-wire, copper conductor, PROTOTHEN®-X (XLPE) insulation with very low dielectric losses, special inner and outer semiconductor layers that homogenize the electrical field, specially added copper screen against high short circuit currents with a suitable cross-section, LSOH outer sheath.
Technical Information
-They are manufactured according to TS IEC 60502-2.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (For short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– Test Voltage (AC): 3.5Uo
Areas of Use
These cables, which have much lower electrical losses than their counterparts, are used in electrical energy supply of residential and industrial areas with high short circuit currents and in networks where load increases are expected, outdoors, in cable ducts, indoors and underground. When specially produced, they are used in fresh and salt water.