- Ana Sayfa
- Prysmian
- Power Cables
- Protodur® Insulated Low Voltage Cables
- YVCV-U / YVCV-R / YVMV / NYCY
YVCV-U / YVCV-R / YVMV / NYCY
Structure
Multi-core, single or multi-wire, copper conductor PROTODUR® (PVC) insulated, concentric copper neutral conductor PROTODUR® (PVC) outer sheathed power cables.
Technical Information
-Manufactured according to TS IEC 60502-1.
– Permissible Operating Temperature: 70 ºC
– Maximum Short Circuit Temperature: 160 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– CPR (Construction Materials Directive) Test: EN 60332-1-2
– Test Voltage (AC): 3.5 kV
Areas of Use
They are generally used underground for city networks, street lighting, home connections and similar purposes. In case of damage to the cables due to digging, the concentric neutral conductor ensures that the switch or fuse at the cable head opens the circuit immediately.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Aynı Markalı Diğer Ürünlerimiz
Structure
Single or multi-core, single or multi-wire copper conductor, special flame-resistant separator layer, special synthetic insulation, galvanized round steel wire armor, special synthetic outer sheath, flame-retardant, halogen-free, non-smoking during fire and continue to function for 180 minutes under flame according to IEC 60331-21. (Armor is aluminum in single-core cables.)
Technical Information
– They are manufactured in accordance with TS IEC 60502-1.
– Permissible operating temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC
– Conductor Structure: Rigid
– LS (Low Smoke) Test: IEC 61034 -1/2
– Burning Droplet Test: IEC 60332-1-3
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C
– FE (Current Conduction) Test: IEC 60331-21
Areas of Use
These cables are used in indoor and outdoor areas such as schools, hospitals, meetings and shopping malls where there are mandatory safety precautions against fire.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Multi-core, single or multi-wire copper conductor, special flame-resistant separator layer, special synthetic insulation, concentric copper conductor, special synthetic outer sheath, flame-retardant, halogen-free, non-smoking and 180 minutes flame-resistant energy and control cables according to IEC 60331-21.
Technical Information
– Manufactured in accordance with TS HD 604 S1 5G.
– Permissible operating temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC
– Conductor Structure: Rigid
– LS (Low Smoke) Test: IEC 61034 -1/2
– Burning Droplet Test: IEC 60332-1-3
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C
– FE (Current Conduction) Test: IEC 60331-21
Areas of Use
These cables are used in indoor and outdoor areas such as schools, hospitals, meetings and shopping malls where there are mandatory safety precautions against fire.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Single or multi-core, single or multi-wire copper conductor, special flame-resistant separator layer, special synthetic insulation, special synthetic outer sheath, flame-retardant, halogen-free, non-smoking and 180 minutes flame-resistant energy and control cables according to IEC 60331-21.
Technical Information
– Manufactured in accordance with TS HD 604 S1 5G.
– Permissible operating temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC
– Conductor Structure: Rigid
– LS (Low Smoke) Test: IEC 61034 -1/2
– Burning Droplet Test: IEC 60332-1-3
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C
– FE (Current Conduction) Test: IEC 60331-21
Areas of Use
These cables are used in indoor and outdoor areas such as schools, hospitals, meetings and shopping malls where there are mandatory safety precautions against fire.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Single or multi-core, single or multi-wire, copper conductor, three or four-core, special synthetic insulated, galvanized round steel wire armored, special synthetic outer sheathed, flame retardant, halogen-free and non-smoking energy cables. (Aluminum in single-core cables.)
Technical Information
– Manufactured in accordance with TS IEC 60502-1.
– Permissible operating temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC
– Conductor Structure: Rigid
– LS (Low Smoke) Test: IEC 61034 -1/2
– Burning Droplet Test: IEC 60332-1-3
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C
– CPR (Construction Materials Directive) Test: EN 60332-1-2
– Galvanized Round Steel Wire Armored
Areas of Use
These cables are resistant to mechanical external effects thanks to the armor consisting of galvanized round steel wires on them. They are used in places where there are mandatory safety precautions against fire.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Single-core, single-wire, multi-wire or fine multi-wire copper conductor, special synthetic insulation, flame retardant and halogen-free energy cables.
Technical Information
– Manufactured in accordance with TS EN 50525-3-31.
– Permissible operating temperature: 70 ºC
– Maximum Short Circuit Temperature: 160 ºC
– Conductor Structure: Flexible
– LS (Low Smoke) Test: IEC 61034 -1/2
– HF (Halogen Free) Test: IEC 60754 – 1/2
– FR (Flame Resistance) Test: IEC 60332-1-2
– CPR (Construction Materials Directive) Test: EN 60332-1-2
Areas of Use
They are used as lighting and installation cables in dry spaces, switchgear facilities, distribution systems, and businesses.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file, or send it to the address you want via e-mail.
Structure
Medium voltage energy cables with single core, multi-wire, copper conductor, very low dielectric loss PROTOTHEN®-X (XLPE) insulation, special inner and outer semi-conductor layers that homogenize the electrical field, specially added copper screen against high short circuit currents, LSOH outer sheath.
Technical Information
– They are manufactured in accordance with TSE K 204 and based on IEC 60502-2.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– Test Voltage (AC): 3.5Uo
Areas of Use
These cables, which have very low electrical losses compared to their counterparts, are used in electrical energy supply of residential and industrial areas where short circuit currents are high and in networks where load increases are expected, outdoors, in cable ducts, indoors and underground. When specially produced, they are used in fresh and salt water.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Medium voltage energy cables with single core, multi-wire, copper conductor, very low dielectric loss PROTOTHEN®-X (XLPE) insulation, special inner and outer semi-conductor layers that homogenize the electrical field, specially added copper screen against high short circuit currents, LSOH outer sheath.
Technical Information
– They are manufactured in accordance with TSE K 204 and based on IEC 60502-2.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– Test Voltage (AC): 3.5Uo
Areas of Use
These cables, which have very low electrical losses compared to their counterparts, are used in electrical energy supply of residential and industrial areas where short circuit currents are high and in networks where load increases are expected, outdoors, in cable ducts, indoors and underground. When specially produced, they are used in fresh and salt water.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Medium voltage energy cables with single core, multi-wire, copper conductor, PROTOTHEN®-X (XLPE) insulation with very low dielectric losses, special inner and outer semiconductor layers that homogenize the electrical field, specially added copper screen against high short circuit currents with a suitable cross-section, LSOH outer sheath.
Technical Information
-They are manufactured according to TS IEC 60502-2.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (For short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– Test Voltage (AC): 3.5Uo
Areas of Use
These cables, which have much lower electrical losses than their counterparts, are used in electrical energy supply of residential and industrial areas with high short circuit currents and in networks where load increases are expected, outdoors, in cable ducts, indoors and underground. When specially produced, they are used in fresh and salt water.
Structure
Three-core, multi-wire, copper conductor, PROTOTHEN®-X (XLPE) insulation with very low dielectric losses, special inner and outer semi-conductor layers that homogenize the electrical field, specially added copper screen with a suitable cross-section against high short circuit currents, flat galvanized steel wire armor and galvanized steel holding tape, LSOH outer sheathed medium voltage energy cables.
Technical Information
-They are manufactured according to TS IEC 60502-2.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– Test Voltage (AC): 3.5Uo
– Galvanized Flat Steel Wire Armored
Areas of Use
These cables, which have very low electrical losses compared to their counterparts, are used in electrical energy supply of settlements and industrial zones where short circuit currents are high and in networks where load increases are expected, outdoors, in cable ducts, indoors and underground. When specially produced, they are used in fresh and salt water.
For product technical specifications and details, you can click on the PDF icon to view the details, download the file or send it to the address you want via e-mail.
Structure
Medium voltage energy cables with single core, multi-wire, copper conductor, PROTOTHEN®-X (XLPE) insulation with very low dielectric losses, special inner and outer semiconductor layers that homogenize the electrical field, specially added copper screen against high short circuit currents with a suitable cross-section, LSOH outer sheath.
Technical Information
-They are manufactured according to TS IEC 60502-2.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– Test Voltage (AC): 3.5Uo
Areas of Use
These cables, which have very low electrical losses compared to their counterparts, are used in electrical energy supply of residential and industrial areas where short circuit currents are high and in networks where load increases are expected, outdoors, in cable ducts, indoors and underground. When specially produced, they are used in fresh and salt water.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Multi-core, multi-wire, copper conductor, PROTOTHEN®-X (XLPE) insulated, galvanized flat steel wire armor, cross-holding steel tape, PROTODUR® (PVC) outer sheathed energy cables.
Technical Information
-Manufactured according to TS IEC 60502-1.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– CPR (Construction Materials Directive) Test: EN 60332-1-2
– Test Voltage (AC): 3.5 kV
– Galvanized Flat Steel Wire Armored
Areas of Use
These cables are very resistant to mechanical external effects thanks to the armor made of flat steel wires on them. They are suitable for heavy operating, laying and assembly conditions. They are used underground and in fresh and salt water when specially produced.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.
Structure
Single or multi-core, single or multi-wire, copper conductor PROTOTHEN®-X (XLPE) insulated, galvanized round steel wire armored, PROTODUR® (PVC) outer sheathed energy cables. (Aluminum in single-core cables.)
Technical Information
-They are manufactured according to TS IEC 60502-1.
– Permissible Operating Temperature: 90 ºC
– Maximum Short Circuit Temperature: 250 ºC (Short circuit time t ≤ 5 sec.)
– Conductor Structure: Rigid
– FR (Flame Resistance) Test: IEC 60332-1-2
– CPR (Construction Materials Directive) Test: EN 60332-1-2
– Test Voltage (AC): 3.5 kV
– Galvanized Round Steel Wire Armored
Areas of Use
These cables are very resistant to mechanical external effects thanks to the armor made of galvanized round steel wires on them. They are suitable for heavy operating, laying and assembly conditions. They are used underground and in fresh and salt water when specially produced.
For product technical specifications and details, you can view the details by clicking on the PDF icon, download the file or send it to the address you want via e-mail.